Installation InstructionsandUser ManualForInverter Power Systems 1.0 - 17.5 KVA
10105. Battery Installation and ConnectionInstalling the Batteries and DC WiringImportant Safety PrecautionsTheinstallermusttaketheseprecautions
11105.1 ToolsThefollowingtoolsarerequiredtoinstallthesystembatteries.Othertoolsmaybenecessaryifoptionalbatterieshavebeen ordered.C
12Installing BatteriesNOTE: ThefollowingprocedureappliestostandardType“S”maintenance-freeLead-Calciumbatteries.LSNsystemsspeciedwith
13Fig. 1BATTERY WIRING DIAGRAM8 BATTERY SYSTEMSCAUTION: Orient all batteries with the positive terminals to the right as shown in the diagram above.
14CAUTION: Orient all batteries with the positive terminals to the right as shown in the diagram above. Carefully observe battery polarity when maki
15CAUTION: Orient all batteries with the positive terminals to the right as shown in the diagram above. Carefully observe battery polarity when maki
161300736 Rev E Fig. 4BATTERY WIRING DIAGRAM36 BATTERY SYSTEMSCAUTION: Orient all batteries with the positive terminals to the right as shown in the
17105.4 Battery Cabinet Voltage Check and DC Fuse InstallationNote:Thisprocedureappliestoa36batterysystem.Fewerstepsmayberequiredde
18106. AC ConnectionsCAUTIONA. AllLSNinvertersystemunitscontainhazardousACandDCvoltages.Becauseofthesevoltages,aqualiedelectrician
195. Ifnotpreviouslydone,removeknockoutsforACInputandACOutputinthetopoftheLSNinvertersystem(SeeFigure1inSection104.1). CAU
2READ AND FOLLOW ALL SAFETY INSTRUCTIONSIMPORTANT SAFEGUARDSWhen using electrical equipment, you should always follow basic safety precautions, includ
20107. RS232 ConnectionsAll LSN inverter systems are supplied with an RS232 communications port. This port may be used for remote monitoring and con
21!109. Maintenance Bypass Switch Phase Check If you are not using a bypass switch with the LSN inverter system, the phase check is not necessary, s
22 CAUTION: If a Make Before-Break type bypass switch is being used, equipment will be damaged if the switch position is changed while AC line vol
23Section 200 User Manual201. User Interface Panel BasicsLED Status IndicatorsAC-On - AC is present at output terminalsReady - Unit is ready for eme
24201.1 Using The Interface PanelThe User Interface Panel is used to display over 250 system parameters, operating modes, alarms and stored logs. Wh
25User Keypad Actions Display Readout[PRG] EnterControlCode Setup Value0 Enter Control Code Setup Value 0 [ENT] PasswordRequired Please e
26201.6 Parameter“HotKey”ListingByFunctionUser changeable parameters are shown in boldface.Metered Parameters: Time & Date (0,10)Inp
27201.6 Parameter“HotKey”ListingByFunctionUser changeable parameters are shown in boldface.Monthly, Yearly Test & Equalize Time Setup:Time
28202. System Self-DiagnosticsSelf-testing/self-diagnosticelectronicsperformcontinuoustestingofsubsystems,insuringperformancetoprescribedo
29203.5 Performing a Manual TestManual5-minutetestsmaybeperformedatanytimeusingthefollowingprocedure:1 Press[PRG],182,[ENT].2. Displ
3Table of ContentsSection 100 System Installation InstructionsDescription Page101. UnitSpecications ...
30Battery Voltage Log (Hot Key # 155)An hourly log of the systems total battery voltage and the charging current. Retains the last 48 entries.081200
31205. Alarms What They Mean And How To RespondWhentheLSNsystemdetectsaproblem,it:• Sounds an alarm• Illuminates the red "ALARM" L
32Alarm Message What it means What to doALM VA Hi 16218 15000 Unit has detected an Remove some of the load until alarm clears. overload and is ab
33206. CommunicationsEachLSNsystemissuppliedwithaDB-9/RS232communicationportenablingtheusertocommunicatewiththeequipmentfromaremo
34Thee-maildeviceautomaticallysendsane-mailtotheaddressesprogrammedwhenever: •Theunitperformsaweekly,monthlyorannualsystemtest
35300. Maintenance300.1 Safe Shut Down ProcedureCAUTIONToavoidpossibleequipmentdamageorpersonalinjury,assumethatthereisACvoltagepresen
36300.2 Routine System Maintenance TheLSNinvertersystemunitisdesignedtoprovideyearsoftrouble-freeoperation.Itsself-testing/self-diagno
37300.4 Battery Maintenance and ReplacementThissectionprovidesprecautionsforqualiedservicepersonnelworkingwithunitbatteries.Nouserser
38CAUTION:A battery can present a risk of electrical shock and high short circuit current. Battery replacement should only beperformedbyqualied
395. Remove the batteries from the cabinet. Batteries can be very heavy, use proper lifting methods when removing battery.6. Install new batteries f
4Section 100 System Installation Instructions101SpecicationsInput• Inputvoltage:120,208,240,277or347VAC+10-15%.Othervoltagesavailableo
40 Param. Keyboard Password No. Type Alpha Level Description 0 Both t User Time 1 Dsp vi N/A InputVoltage 2 Dsp vo N/A O
41 Param. Keyboard Password No. Type Alpha Level Description 168 Both hvoe Serv E/DHiOutputVoltsAlarm 169 Both hvie Serv E/D
42Notes: 268 Both gwa User Gatewayaddress 269 Both snm User Subnet mask 270 Disp em1 N/A E-mailaddress1 271 Both em2 User E-mai
43Notes:
44A Hubbell Lighting, Inc. brand with representatives' offices in principal cities throughout North America. Copyright © Hubbell Lighting, Inc.
5102. Receiving, Moving and Storing Systems and Batteries 102.1 Shipping DamageLSN inverter systems and batteries are normally shipped separately.Ca
6103. Installation Requirements103.1 Operating EnvironmentInstalltheLSNinvertersysteminaclean,cool,dryplacewithnormalventilationforhu
7104. Cabinet Mounting104.1 DimensionsTable 104A - Dimensions: Unit and Battery Cabinets Width (A) Height (B) Depth (C) Footprint 30 in. 46 in.
8Fig. 1 Fig. 2Fig. 3 Fig. 4104.3 Cabinet InstallationBasedonthedesiredcabinetcongurationfortheapplication,removetheappropriateknockouts
9Install Wall Mounting Brackets To Top Cabinet On Both Sides Conguration“A”TwoCabinet SystemsInstall Wall Mounting Brackets To Top Cabinet On Both S